Case Study: Melbourne Electrical Fault

Thermal Scanners were contacted to perform Thermal Imaging on a tavern located in Melbourne in order for them to maintain their insurance policy.  The Melbourne tavern was constructed within the last 20 years and had a relatively modern electrical system in place with a total of 5 switchboards including:

  • Main Switch Board With 2 sections,
  • 2 x Distribution Boards, and
  • TAB Sub Board

In order to perform the most accurate survey, Thermal Scanners organised to conduct the thermal survey during the busy lunch period for the Melbourne tavern, in which the largest amount of electrical load would be on the site.  It was noted that the site was drawing large electrical load due to the temperatures found on the Main Isolator being 50°C, whereas a low load would cause the Isolator to be closer to ambient temperature.

Main Isolator Under A Heavy Electrical Load

The elevated temperature is not a problem as this is still operating well within the operating temperatures of both the isolator and cable, however it is good to note that the survey will be performed under sufficient load.  When completing a Thermal Imaging Survey, Thermal Scanners also complete a visual check of all the boards, cables and equipment to ensure that they are safe and have no damage such as corrosion, evidence of a fire and that the boards are appropriately secured.  The Melbourne Tavern had no visual faults during the survey, however when carrying out the Thermal Survey a hot spot was located on the Neutral Bar.

Hot Screw Connection On Neutral Bar

This fault found on the Melbourne Taverns Neutral Bar is what we would categorise as a level 2 thermal exception requiring investigation in the very near future.  At first it appeared like this fault was most likely due to a loose connection where the connecting cable is loose and creating a high resistance location.  Although when examined closer in the visual spectrum we can see that the screw used is actually of a different material composition.

Neutral Bar, Incorrect Screw Material

These two different materials connecting and passing electrical current through them create a hot resistance connection.  This problem is then a simple rectification for the Melbourne Tavern to have their preffered electrical contractor attend site and replace the neutral bar screw to the correct material composite.

If you want any more information on a Thermal Survey, or the work that we perform then don’t hesitate to reach out through our website.

Electrical Thermography

What is Electrical Thermography?

Electrical Thermography is the detection of heat within electrical components, terminations and wiring of electrical infrastructure such as switchboards.  The detection of the heat is completed with the use of an infrared scanner which is a specialised camera.  The camera creates an image that can be interpreted by a trained operator to quickly identify problem areas, components or connections.

Electrical Thermography is utilised to examine the health of the electrical systems through a non-invasive and non-destructive testing method that is completed whilst the power is active.  It helps to identify hotspots that can indicate potential problem areas where dangerous failures such as fires may occur.  As Electrical Thermography is a non-contact method of fault finding, there is no interruption to the power supply or shutdowns required to complete the work.

Read more about how electrical thermography is used in Melbourne.

What causes the problems in electrical systems?

  • Underrated cables/equipment
  • Rust and degradation
  • Unbalanced loads
  • Loose terminations
  • Malfunctioning equipment

In this example, a three-pole circuit breaker was found to be operating at close to its maximum temperature limit.  This was most likely due to the use of an underrated component for the amount of load required within the circuit.  If this problem had not been identified there was a very real risk of having this fail during the operation of the warehouse causing a costly shutdown while the problem was identified and rectified.

Electrical Thermography
Three Pole Circuit Breaker at Elevated Temperature, Detected Through Electrical Thermography

What are some of the benefits of Electrical Thermography?

  • Planning downtime for repairs during non-peak times to avoid interruption
  • Identify overloaded circuits or underrated cables
  • Reduce the cost of repairs by only replacing faulty components
  • Minimise the risk of fire and damage due to failure of components
  • Ensure the longevity of components through balanced loads
  • Obtain insurance and reduce the premiums

Now that we understand some of the benefits of having Electrical Thermography completed on our electrical systems, we need to also understand what infrastructure and boards should be scanned.  

What Boards need to be scanned?

  • Switchboards
  • Fuse boxes
  • Control panels
  • Mechanical services boards
  • Power factor correction units
  • Main Switch Boards (including all panels and sections)
  • Sub-boards

What happens once the Electrical Thermography is completed?

When Thermal Scanners complete the Electrical Thermography work, the on-site technician will inform the site contact/manager of any major problems identified during the scan.  From here insurance compliant report is completed that will detail all thermal anomalies on site and provide an overall picture of the health of your electrical infrastructure by providing at least 10% of all boards captured and analysed.  The report is then checked for accuracy and quality by our head office before being sent off within a one-day turnaround window.

Insurance Requesting a Thermal Scan

Why has my insurance requested Thermal Imaging?

There has been a recent trend of insurance companies requesting for businesses and companies to complete thermal imaging of their electrical boards within their operations to either receive insurance or reduce premiums, so why is that?  Thermal imaging can help locate electrical faults and problems before they cause a major failure such as a fire or loss of operations.

 

How Does It Work?

Thermal Imaging works by using a special type of camera that detects infrared radiation and converts this into temperatures.  Using these cameras, qualified and licensed thermographers are able to detect faults on electrical components before they fail.  Some of these faults can include:

  • Loose / improper terminations
  • Faulty components
  • Overloaded circuits
  • Unbalanced loads
  • Undersized connections and cables

Each of these above mentioned faults will create a different thermal pattern on the electrical equipment so it is vital that you utilize thermographers who are licensed and experienced in order to correctly examine and identify if a fault exists.  The below photo shows a circuit breaker with the red phase having a large elevation in temperature indicating either a loose / improper termination or an unbalanced load.

Termination or unbalanced load Fault on circuit breaker

Insurance Requirements.

When your insurance company requests Thermal Imaging of your electrical equipment there are a few things that are required to ensure that you receive an insurance compliant thermal scan, these include:

  • Licensed thermographer with a minimum of Level 1 qualifications,
  • Insurance compliant report that notes and details all thermal exceptions,
  • Detailed scope of works that includes location and description of on-site boards and equipment.

Many electricians offer to complete Thermal Imaging however, often they don’t hold at minimum a level 1 thermography qualification and as such insurers may require this to be completed again by a thermographer.  Further, many smaller and non specialised companies may not produce reports that meet insurance standards. 

 

At Thermal Scanners we ensure that all our field staff are certified thermographers with a minimum of a level 1 qualification and all our reports are checked for quality in our head office before issuance.  This ensures that all work completed is inline or exceeds insurance requirements to give our clients peace of mind.  

 

Contact us today for a quote or for more information on insurance Thermal Imaging.

Case Study: Electrical Faults at Industrial Sites

During a recent annual routine electrical thermal scan of a major industrial worksite, Thermal Scanners helped to locate and identify multiple major faults within the existing electrical infrastructure.  Some of these included excessive temperature located on Isolators, Circuit Breakers, Overload / Contactor setup and relays.  Thermal Scanners’ completes scanning of this site yearly, and due to the high level of power demands and usage, different components experience problems every year.  The previous year six faults were identified whereas during this year of scanning 13 faults were found.

High level fault on 250 Amp Isolator identified during Thermal Scanning

One of the major faults found on site was on an overloader / contactor setup which controls the fans for a crucial cooling stack.  If this cooling stack had broken, it would have caused a complete site shutdown while the fault was found, identified and rectified.  Further as the fault was at such a high range, the potential for an electrical fire was very real, which could have caused millions of dollars in damage.

High level fault on a overloader / contactor setup found during Thermal Scanning

The temperature of the above overloader / contactor setup was causing excessive temperature in both of the adjacent components, which will reduce their lifespan and cause additional costs for maintenance and replacement.  Pictured below is the contactor which shows the inside of the component beginning to burn and melt the casing.

Inside of the contactor identified in the thermal scan above

Thermal Scanners were still on site after replacement of the component, as such we completed another scan on the affected electrical board. It was found that the problem had been resolved and the adjacent components were running at normal operating temperature. Due to the company utilising thermal scanning they were able to replace a faulty component that was going to experience imminent failure before causing a site wide shutdown.

Case Study: Solar Panel Thermal Imaging

Thermal Scanning is able to detect faults with photovoltaic solar systems that can’t be picked up by the naked eye.  During adverse weather events such as hail or large winds, solar panels can become damaged causing damage to either individual solar cells, strings of cells or entire panels. Thermal Scanners were contracted to find faults on a small residential solar system as previous tradespeople had been unable to determine which panels were the problem.  When on site multiple panels had been marked due to minor cracking from the hail, these are shown by the coloured circles in the thermal images below.

Solar Panels Without Faults

Thermal Imaging Of solar panels without any faults detected
Thermal Imaging Of solar panels without any faults detected

These thermograms show that during scanning there were no thermal faults detected on either of these panels even though a previous tradesperson had recommended replacement of both of these.  Problems appear on solar panels as either individual cells or a string of cells showing abnormal temperature compared to the rest.

Faulted Solar Panel

Thermal Imaging Of solar panels with a single faulty cell

The above image shows where a fault was identified on the residential solar system with an elevated temperature on a single cell.  In total Thermal Scanners identified two panels that had thermal faults whilst the tradesperson identified 8 – 10 panels.  This allowed the client to replace only the fault panels and have there solar system working at peak performance with the lowest cost to fix.

If you require scanning of your solar panels then please contact us for a no obligation quote today

Quantitative vs Qualitative Thermography

There are two main types of thermal screening analysis that can be completed.  These are quantitative and qualitative, where quantitative aims to find the exact temperature of a component and qualitative compares similar components to find faults.  Most thermal surveys will be completed in a qualitative manner due to the additional technical hurdles involving emissivity which increase the associated costs. Certain fields of thermography lend themselves to qualitative inspections; especially electrical thermal scanning and mechanical thermal imaging, as there are similar components to compare each one to.  These technical hurdles include knowing the materials true emissivity, atmospheric conditions and utilising angles of incidence.

Is Qualitative accurate?

The simple answer is yes!  This is because when completing a thermal scan in a qualitative manner components are being compared to one another and the difference in operating temperatures is what is being considered.  Another way to consider this is that when looking at components in an electrical board (such as the photo below) the same components will all have the same emissivity and be under the same atmospheric conditions such that their baseline temperatures are all factored by the same amount.

thermography

Above is a qualitative analysis and as can be seen there is a very noticeable difference in temperature between the same components.  Showing that there is a fault on the centre component.

thermography

Why is Quantitative analysis so much more difficult?

When attempting to gather accurate temperature data, the exact atmospheric conditions present must be known such as; humidity, ambient temperature and reflected temperatures.  In addition the distance from the imager to the components must be known.  These are able to be gathered accurately through the assistance of other equipment such as anemometers (pictured right).  

However, the most important and hardest to account for is the materials emissivity.  This is because the emissivity of an object changes depending on various factors such as; what the component is made of, the components surface texture and even the exact temperature it is at.

How can thermographers account for all this?

Depending on the accuracy requirements thermographers can utilise emissivity tables which will give estimates for materials, (such as this one https://www.sika.net/images/Documents/Table_of_Emissivity.pdf).

As can be seen in the table, even aluminum can vary from .02 -> .40.

Luckily thermographers have another way to overcome these limitations, we can utilise other materials such as specialised high-emissivity tape or sprays which will bring the emissivity close to a more controlled value that is known. However this is usually a length process as the thermographer has to either apply the tape or spray to a component (which must be turned off!) or to an adjoining location and calculate the relative emissivity.

Case Study: Electrical Hottest Fault

Thermal Scanners conduct hundreds of thermal scans per year at locations all around Australia. As such we are used to seeing faults regularly that surprise our clients. Sometimes the faults we find on site even shock us. This is because the faults can reach extreme temperatures that show failure is imminent.

Below we will show some of the highest temperature faults that we have found on a variety of sites, ranging from body corporates, private organisations and public buildings.

Fuse Holder above 100°C

Most often when we find thermal exceptions they appear on the terminations that connect to the cables.  However this fault extends to the actual component, in this case a fuse.  The fuse pictured below is designed to operate up to 80°C when there are no other fuses directly next to it.

Thermal fault on a fuse.

In this case the fuse is actually the hottest part and is operating well beyond its operating temperature, which potentially could have been life threatening as it has not tripped indicating there could be a problem in the circuit.  A visual image of this fault is shown below which shows the physical burns and damage to the fuse holder.

Even with the fuse burnt and damaged the circuit above is still live, active and complete!

Contactor above 200°C

In our work Thermal Scanners has found that sometimes cables have been physically burnt or damaged and yet at the time of scanning there is no load and hence no excessive temperature.  In the follow photo this is not the case and the component is still under load and has burns far beyond the typical:

Thermal fault on contactor

The above thermal image shows a maximum temperature in excess of 200°C and this is conservative due to our emissivity settings.  It can be seen that the cable is also above 100°C for a considerable length beyond the termination. Even the adjacent cable is affected by this heat!  To better show the effect of this increased heat we have also included a visual photo.

Visual photo of burns to cable

As can be seen the fault has actually caused the insulation on the cable to melt, exposing live electrical wires. Further it has begun to melt and damage the components outer casing.  If this fault was not detected an electrical fire may have resulted as soon as the next couple of days.

Circuit Breaker Above 500°C

In 2020 we completed Thermal Imaging on a customers commercial premise and during completion of the service we found a thermal exception on the wire and termination of a 3 phase circuit breaker. 

Thermal fault over 500°C on circuit breaker

Keep in mind that most circuit breakers have an operating temperature of up to 85°C including these ones manufactured by Heinemann.  With a maximum temperature in excess of 500°C this circuit breaker is operating at almost 6x its maximum recommended temperature and will almost certainly cause an electrical fire!

We hope that seeing some of these faults helps individuals and companies understand why annual thermal imaging is required on switch boards.  If any of the above faults were not detected these could have easily caused large scale loss of power and even caused an electrical fire in the immediate future with serious ramifications.

Cold Room Leakage – Case Study

Thermal Scanners were contracted to try and locate a problem with an existing cold room installation before the completion of sale.  The installation consisted of a small walk-in freezer at a restaurant.  

Water damage was found in the access corridor outside the business causing large damage to the external wall and constant water pooling on the floor. Further to this the freezer was not holding its temperature sufficiently.

During the thermal leakage scan Thermal Scanners were able to identify a fault in a corner of the freezer where the floor and walls connected. The fault pictured below had a temperature variance of more then 9°C compared to every other surface.  This fault was not able to be detected visually, as there was no cracking or separation evident in the corner or along the corner wall seam. This thermal pattern potentially means the insulation in the corner and potentially under the floor had failed causing large thermal leakage.

Fault found in corner of Walk-in Freezer
Thermal Leakage of a Corner Connection In Walk-In Freezer

Once the repairs had been completed a further scan was completed and showed no thermal leakage, in addition the water leakage was no longer occurring, most likely the thermal leakage was causing condensation on the internal side of the wall which is known as “sweating”.  

Thermal Scanners can provide a fault only report, within 2 business days from scanning, that will outline in detail all thermal exceptions that are found. In conjunction with this service, we can also complete the thermal imaging of your electrical equipment whilst our technicians are on site, to reduce costs.

Thermal Scanning Electrical

Thermal Scanning is the use of a thermal imager to detect heat energy, which can then be converted into a visible image (for more detail see What Is Thermal Scanning).  One of the major applications for thermal imaging is to verify the health of electrical systems, leading to early detection of faults, even before the human eye can see them.  

Why can thermal scanning be used on electrical systems?

Thermal scanning can be utilised on any electrical system as it creates heat energy as a waste byproduct, or sometimes even as the main purpose such as a heater! Both heat and electrical energy are measured in the same way; joules of energy or watts if we account for time.  The amount of energy is directly proportional to the amount of voltage and current being used.

Thus, when we examine a 20 Amp fuse operating at more than 20 Amps of current with a thermal camera, we can see the elevated temperature when compared to other similar components.  In this case the amount of current was verified by attaching a clamp meter and measured at 30 amps; indicating that either the fuse needs to be resized or the load rebalanced to ensure an optimal electrical configuration.

Electrical Thermal Scanning
Electrical Thermal Scanning of an over-loaded Fuse

What benefits are there of getting thermal scanning completed on my electrical infrastructure?

As mentioned, thermal scanning is able to pick up issues before they become apparent to the naked eye.  Some of these benefits include:

  • Minimising the risk of fire and damage due to failure of components,
    • Which ensures peace of mind for you as the owner.
  • Reduce cost of repairs by only replacing faulty components,
    • When the location of a fault is known the component can be replaced or repaired quickly without having to replace multiple items!
  • Scheduling in shutdowns so they can be completed with other works,
    • As we find faults early, this allows problems to be fixed with other routine maintenance.
  • Preventing unexpected loss of power,
    • When components fail they can either do so by catching fire, exploding or just failing.  Some of these are worse than others, but all will result in the loss of power potentially costing millions of dollars in down time.
  • Identify overloaded circuits or under rated cables, and
    • When cables and fuses aren’t rated properly the chances of failure increase, however thermal scanning can detect these problems quickly and efficiently.
  • Ensuring longevity of components through balanced loads.
    • Unbalanced loads are one of the more common problems in electrical,  where the phases haven’t been balanced causing excessive heat generation through specific components.

Thermal imaging can detect a range of different problems with electrical infrastructure which can range from the obvious overheating components to something as simple as loose and poorly terminated connections.  Some of the major ones we encounter on a daily base include:

  • Loose terminations,
  • Underrated cables,
  • Rust and degradation,
  • Unbalanced loads, and
  • Malfunctioning equipment.

To help put into perspective how bad some of these faults can be even before failure, we have provided an image of one of the worst thermal faults we have ever found with a peak temperature above 500°C!

Even in the above photo (without feeling the heat), it would be extremely difficult to detect this fault without the use of thermal imaging, even though this component is about to fail and potentially catch fire!